PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
E-6 Installing a Communication Adapter
5. Disconnect the HIM Communication cable from the connector on the
upper right corner of the Control board and set the cover aside.
6. Secure and ground the Communication Adapter to the EMI Shield on
the drive using the four captive screws.
Important:All screws must be tightened, because the adapter is
grounded through a screw to the EMI shield.
Recommended tightening torque is 0.9 N•m (8 lb•in).
7. Connect the Internal Interface cable to the DPI connectors on the
Control board and the communication Adapter board.
8. Refer to the Adapter’s User Manual for network connection,
commissioning, and configuration information.
Pull tabs out
to disconnect
cable.
=
All Frames (Frame A shown)
=
Secure adapter to
EMI Shield with
four (4) screws.
Connect cable to
DPI connectors
on adapter and
control board.