Input and Output Connections
34 AC-825IP Hardware Installation and User Guide
Figure 28: Normally Closed Supervised Input (Double Resistor)
4.2 Inputs Description
4.2.1 Request-to-Exit Button (REX) Input
Use the REX Input to open a door directly. Typically, the REX input is connected
to a Normally Open push button that is located inside the premises. The push
button is generally located in an easy-to-access position and opens a door
without reading any credential.
Scenario Setting
Two Readers per Door
Door 1 IN 1A
Door 2 IN 3A
Door 3 IN 5A
One Reader per Door
Door 1IN 1A
Door 2IN 2A
Door 3 IN 3A
Door 4 IN 4A
Door 5 IN 5A
Door 6 IN 6A
REX Inputs functions when using D-805:
Scenario Setting
Two Readers per Door
Door 4IN 1C
Door 5IN 3C
One Reader per Door
Door 7IN 1C
Door 8IN 2C
Door 9IN 3C
Door 10IN 4C
4.2.2 Door Monitor Input
The Door Monitor Input typically connects to a Normally Closed door sensing
micro-switch for door status monitoring. Using Door Monitor enables many
advanced options such as door forced alarm, door held open warnings,
interlocking doors and more.

Table of Contents

Other manuals for Rosslare AC-825IP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rosslare AC-825IP and is the answer not in the manual?

Rosslare AC-825IP Specifications

General IconGeneral
BrandRosslare
ModelAC-825IP
CategoryController
LanguageEnglish

Related product manuals