VM1000 Series
‐94‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F8.30
Given frequency
reached 1
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz ☆
F8.31
Given frequency
reached detection
width 1
0.0%~100.0% (Maximum
frequency)
0.10% 0.00% ☆
F8.32
Given frequency
reached 2
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz ☆
F8.33
Given frequency
reached detection
width 2
0.0%~100.0% (Maximum
frequency)
0.10% 0.00% ☆
F8.34
Zero current
detection level
0.0%~300.0%, 100.0% is
corresponding to motor rated
current, No output in stop status.
0.10% 5.00% ☆
F8.35
Zero current
detection time
0.01s ~ 600.00s 0.01s 0.10s ☆
F8.36
Programm over
current setting
0.0%: No detection
0.1%~300.0% Motor rated current
0.10% 200.00% ☆
F8.37
Programm over
current detection
time
0.00s ~ 600.00s 0.01s 0.00s ☆
F8.38
Given current
reached 1
0.0% ~ 300.0% Motor rated
current
0.10% 100.00% ☆
F8.39
Given current
reached detection
width 1
0.0% ~ 300.0% Motor rated
current
0.10% 100.00% ☆
F8.40
Given current
reached 2
0.0% ~ 300.0% Motor rated
current
0.10% 100.00% ☆