EB 8384-2 EN 107
Operating the positioner
By entering the blocking position (Code 35), closing direction (Code 34), pin position (Code
4), nominal range (Code 5) and direction of action (Code 7), the positioner can calculate the
positionerconguration.
Perform a reset before re-initializing the positioner if the substitute positioner has already
been initialized. Refer to section7.9.
Enable conguration:
Ifnosettingsareenteredwithin120seconds,theenabledcongurationfunctionbecomesin-
valid.
1. Turn untilCode3appears(reading:
No).
2. Press , the code number 3 blinks.
3. Turn
until YES appears.
4. Press
toconrm(reading: ).
Enableconguration
Default: No
Enter the pin position and nominal range:
1. Turn untilCode4appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press toconrm.
5. Turn
untilCode5appears.
6. Press
, the code number 5 blinks.
7. Turn
and set nominal travel of the valve.
8. Press
toconrm.
mm
Pin position
Default: No
mm
Nominal range
(lockedwhenCode4=
No)
NOTICE
!