108 EB 8384-2 EN
Operating the positioner
Select the initialization mode:
1. Turn untilCode6appears.
2. Press
, the code number 6 blinks.
3. Turn
until SUb appears.
4. Press
toconrmtheSUbinitialization
mode.
Init mode
Default: MAX
Enter the direction of action:
1. Turn untilCode7appears.
2. Press
, the code number 7 blinks.
3. Turn
to select the direction of action
(ää/äæ).
4. Press toconrm.
Direction of action
Default:
Deactivate travel limit:
1. Turn untilCode11appears.
2. Press
, the code number 11 blinks.
3. Turn
until No appears.
4. Press
to deactivate the travel limit func-
tion.
Travel limitation
Default: No
Change pressure limit and control parameters:
Do not change the pressure limit (Code16). Only change the control parameters K
P
(Code
17) and T
V
(Code 18) if the settings of the replaced positioner are known.
Note