EasyManua.ls Logo

Samsung DVM Plus 2 Series - Page 410

Samsung DVM Plus 2 Series
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating Instructions and Installation
11-29Samsung Electronics
A B
C
D
Fixed Fixed Digital
A When installing more than 1 outdoor unit
and first Y-joint
B Among the outdoor units
C Outdoor unit connection
D Oil balancing pipe
Selecting the refrigerant pipe
A
Installing pipes between more than
1 outdoor unit and first Y-joint
- Select the size depending on the
outdoor unit capacity.
8
10
12,14
16,18,20,22,24
26,28,30,32,34
36,38,40,42,
44,46,48
ø9.52
ø9.52
ø12.70
ø15.88
ø19.05
ø19.05
ø19.05
ø22.23
ø25.40
ø28.58
ø31.75
ø38.10
Outdoor unit total
capacity (HP)
Gas side
(mm)
Liquid side
(mm)
Selecting the refrigerant pipe
A
Between Y-joints
- Select it depending on attached
indoor units.
X < 22.4
22.4 X < 33.0
33.0 X < 47.0
47.0 X < 71.0
71.0 X < 104.0
104.0 X
ø9.52
ø9.52
ø12.70
ø15.88
ø19.05
ø19.05
ø15.88
ø22.23
ø25.40
ø28.58
ø31.75
ø 38.10
Indoor unit total
capacity (kW)
Gas side
(mm)
Liquid side
(mm)
B
Among the outdoor units
- Depend on the total capacity of
attached outdoor units.
X < 26
26 X < 36
36 X
ø15.88
ø19.05
ø19.05
ø28.58
ø31.75
ø38.10
Outdoor unit
capacity (HP)
Gas side
(mm)
Liquid side
(mm)
C
Outdoor unit connection
- Depend on the outdoor unit
8
10
12,14
ø9.52
ø9.52
ø12.70
ø19.05
ø22.23
ø25.40
Outdoor unit
capacity (HP)
Gas side
(mm)
Liquid side
(mm)
D
Oil balancing pipe
- Applicable only 16HP or more
X 16 ø6.35
Outdoor unit
capacity (HP)
All diameters (mm)

Table of Contents