EasyManuals Logo

Samsung DVM Plus 2 Series User Manual

Samsung DVM Plus 2 Series
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #428 background imageLoading...
Page #428 background image
Troubleshooting
12-17Samsung Electronics
: Compressor Sump Temperature Protection Control
1.
Check Method
Outdoor unit display
Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost)
Judgment method Sump temperature maintains for over 5 minutes over 95°C
Causes Compressor loading inferiority / Sump temperature sensor inferiority
Error reset (Key 3)
Test operation(Same condition of
error occurrence)
Check the compressor that the
error is occurred through S-net.
Separate the temperature
sensor from the compressor and
leave it on the air for approximately
10 minutes.
Reattach the temperature sensor
Complete the check.
Is the Loading or Unloading of the Digital
compressor operated normally?
Is the temperature sensor attached correctly?
Is the Sump temperature
value similar as the outdoor
temperature value?
S-net connection (Requisite)
Check the PWM Valve.
Check the temperature sensor
attachment.
Replace the relevant
temperature sensor
No
No
No
Yes
Yes
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM Plus 2 Series and is the answer not in the manual?

Samsung DVM Plus 2 Series Specifications

General IconGeneral
BrandSamsung
ModelDVM Plus 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals