Troubleshooting
12-29Samsung Electronics
, ,
: Compressor Emission Temperature Sensor Breakaway
Must organize because the location of the compressor Discharge temperature sensor is different by the error code.
1.
Check Method
After checking whether the relevant compressor sensor is broken away by the error code or not, assemble and adjust.
In case of the main outdoor unit:
(Digital compressor), (Fixed1 compressor), (Fixed2 compressor)
In case of the sub outdoor unit:
(Fixed1 compressor), (Fixed2 compressor), (Fixed3 compressor)
Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost)
1) Relevant compressor current value (CT sensor value) is over 5A.
2) Relevant compressor emission temperature < High pressure saturation temperature
When detect the above 1) and 2) conditions are detected for over 30 minutes continuously
Causes Compressor Discharge sensor breakaway error / Sensor defect
Outdoor unit display
Judgment method
Are the emission
temperature sensor and
holder attached correctly?
Is the emission
temperature sensor resistance value proper?
(Refer to )
Is the sensor insertion location
correct by the compressor order?
Reinsert the sensor.
Reattach the sensor holder.
Sensor defect : Replace the sensor
Sensor is inserted incorrectly:
Change the sensor location
Complete
No
No
No
Yes
Yes
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM Plus 2 Series and is the answer not in the manual?

Samsung DVM Plus 2 Series Specifications

General IconGeneral
BrandSamsung
ModelDVM Plus 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals