Troubleshooting
12-65Samsung Electronics
: COND OUT sensor breakaway
Outdoor unit display
Indoor unit display
Judgment method
Causes
(COND OUT sensor)
(Operation) (Timer) (Fan) (Filter) (Removing frost)
- Refer to the below judge method
- Indoor heat exchanger COND OUT sensor breakaway
1. Judge method
1) Not detected on cooling operation
2) Cond Out Sensor is detected in the condition that it is under heating test operation and the capacity of compressor is
the maximum ste (20 step).
3) Heating operation (The following conditions should be satisfied for 20 minutes.)
2. Check method
Check if the corresponding outdoor unit COND OUT sensor is separated according to the error code, assemble and
adjust it.
Teva, in - Tair, in 3˚C
Teva, out - Tair, in 2˚C
Tcond, out - Tair, out < -2˚C
Compressor running &
indoor unit on and thermo on
Error contents
OK
OK
NO
OK
Outdoor unit COND OUT sensor breakaway