Troubleshooting
12-67Samsung Electronics
: The compressor discharge temperature sensor breakaway
You shall classify the position of compressor discharge temperature sensor according to the below code.
1. Judgment Method
If digital compressor discharge temperature is Tdisc, d
Fixed compressor discharge temperature are Tdisc, f1/tdisc, f2/Tdisc, f3,
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E262 error
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E263 error
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E264 error
2. Check method
Check if the corresponding compressor sensor is separated according to the error code, assemble and adjust it.
Display method of the order and number of compressor (In case of 4 compressors)
Front
Digital compressor
Control Box
Control Box
!
@
#
$
Outdoor unit display
Indoor unit display
Judgment method
Causes
(Digital Compressor)
(Operation) (Timer) (Fan) (Filter) (Removing frost)
- Refer to the below judge method
- Compressor discharge temperature sensor breakaway

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM Plus 2 Series and is the answer not in the manual?

Samsung DVM Plus 2 Series Specifications

General IconGeneral
BrandSamsung
ModelDVM Plus 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals