Troubleshooting
12-69Samsung Electronics
, : Prohibit to start compressor according to the outdoor temperature
Outdoor unit display
Indoor unit display
Judgment method
Causes
(30˚C over of outdoor temperature on heating mode)
(-5˚C below of outdoor temperature on cooling mode)
(Operation) (Timer) (Fan) (Filter) (Removing frost)
- If the outdoor temperature is below -5˚C at the right before of compressor start,
- prohibit cooling operation.
- If the outdoor temperature is over 30˚C at the right before of compressor start,
- prohibit heating operation
- Operation prohibit mode according to the limit of outdoor temperature
Check method
The above error code is not the products error, but specification to protect the products by restricting the use temperature
ranges. Use it by reference to the temperature range of use condition in manual.
If the above error code is occurred despite of condition being not included above judge method, read the value of outdoor
inlet air temperature by use of view mode or S-net. And then if it is different with the actual outdoor temperature, replace the
temperature sensor.