EasyManuals Logo

Samsung mini DVM Series User Manual

Samsung mini DVM Series
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #446 background imageLoading...
Page #446 background image
Troubleshooting
12-35Samsung Electronics
Indoor Unit EVAP IN Sensor Error (Open/Short)
Outdoor unit display A*** (***: Indoor unit address which an error is occurred)
Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost)
Judgment method Refer to the below Judgment Method
Causes Open/Short error of the no. *** indoor unit EVAP IN sensor
Is separated the indoor
EVAP IN sensor connector
from PCB?
Is the resistance value
far from the
temperature table?
Detach the indoor EVAP IN
connector from PCB and measure the resistance
value between the both terminals.
Restart after replacing PCB.
Restart after connecting a
connector to PCB.
Replace the indoor EVAP IN sensor
because it is defect.
Yes
Yes
Yes
No
No
Temperature
(°C)
70
60
50
40
30
20
10
0
-10
Resistance
(KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung mini DVM Series and is the answer not in the manual?

Samsung mini DVM Series Specifications

General IconGeneral
BrandSamsung
Modelmini DVM Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals