Troubleshooting
Samsung Electronics12-36
Indoor Unit EVAP OUT Sensor Error (Open/Short)
Outdoor unit display A*** (***: Indoor unit address which an error is occurred)
Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost)
Judgment method Refer to the below Judgment Method
Causes Open/Short error of the no. *** indoor unit EVAP OUT sensor
Is separated the indoor EVAP OUT
sensor connector from PCB?
Is the resistance value
far from the
temperature table?
Detach the indoor EVAP OUT
connector from PCB and measure the resistance
value between the both terminals.
Restart after replacing PCB.
Restart after connecting a
connector to PCB.
Replace the indoor EVAP OUT sensor
because it is defect.
Yes
Yes
Yes
No
No
Temperature
(°C)
70
60
50
40
30
20
10
0
-10
Resistance
(KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0