2.3 SCHEDULED MAINTENANCE
If installed in an adequate place, the converter scheduled maintenance is reduced to a minimum. The
minimum maintenance intervals are indicated in the table below.
Maintenance tasks
Minimum frequency
What to do
Check heatsink;
clean, if required
Depending on dust concentration
(every 6…12 months)
See Heatsink section below
Check cooling fans;
replace, if required [*]
Depending on dust concentration
(every 6…12 months)
See Cooling fans section below
Replace cooling fans [*]
Every 6 years
See Cooling fans section below
[*] on models with forced air cooling only, i.e. from DCREG.100 and greater.
Heatsink
The cooling fans in the DCREG build up dust from air intake.
Check if the heatsink is clean.
If the heatsink needs to be cleaned, please contact Elettronica Santerno Customer Service.
Cooling fans
The minimum expected durability of the cooling fans of the DCREG is approx. 50,000 hours. Actual
lifetime is based on the operating conditions of the converter, the ambient temperature and the
environmental pollution.
The signs for imminent possible failures are noisy bearings of the fans or worn fins of the fans although
regularly cleaned.
If the DCREG is used in a crucial stage in a process, consider replacing the cooling fan as soon as these
symptoms occur.
Please contact Elettronica Santerno Customer Service to replace the cooling fans.