7.2.80 P230: MIN. FIRING ANGLE
DCREG4: 30.0°
DCREG2: 25.0°
Min. delay angle for the thyristor firing and the energy transfer from the mains to
the load.
This is the limit for parameter M005 (Alfa) when the drive operates as “motor”.
7.2.81 P231: MAX. FIRING ANGLE
Max. delay angle for the thyristor firing and the energy transfer from the load to
the mains.
This is the limit for parameter M005 (Alfa) when the drive operates as “brake”.
7.2.82 P240: LOW PASS FILTER OVER THE SPEED / VOLTAGE
ERROR
This parameter expresses, in milliseconds, time constant of the low pass filter
for the first speed error operating according to the following transfer function:
7.2.83 P250: UP / DOWN INTERNAL REFERENCE POLARITY
This parameter sets the allowable polarity for the UpDownRef internal reference.
See also the MOTOR POTENTIOMETER chapter.
0:Bipolar. Bipolar reference.
1:Positive only. Positive reference only.
2:Negative only. Negative reference only.
7.2.84 P251: UP / DOWN INTERNAL REFERENCE RESTORATION AT
POWER ON
If set at default value 1:Yes, this parameter restores the last value stored for the
UpDownRef internal reference before or a power failure or the device power off.
Otherwise (0:No setting) this internal reference will always restart from zero. See
also the MOTOR POTENTIOMETER chapter.
0:No. Reset zero value at power on.
1:Yes. Restoration at power on.