7.3.51 C163: MASTER DATA AREA BASE ADDRESS
C163 BaseAddress
P
C163 - BaseAddress
# *****
R
# 0 ... 32767
D
# 0
F
This parameter indicates the correspondence between the drive data area and
the master data area.
7.3.52 C164: SERIAL TIME OUT
C164 RTUTimeOut
P
C164 – RTUTimeOut
**** ms
R
0.00 … 2000 ms
D
300. ms
F
This parameter indicates, in milliseconds, the timeout of the drive (time out)
while receiving an additional character, before considering the inquiry
transmitted by the master a concluded message.
7.3.53 C165: SERIAL RESPONSE DELAY
C165 RxTxDelay
P
C165 - RxTxDelay
**** ms
R
0.00 … 2000 ms
D
0.00 ms
F
This parameter concerns the half duplex transmission mode only, like the two-
wire RS485 standard. It defines, in milliseconds, the delay time of the drive
before its response to a master inquiry, to make sure that the latter has already
switched to the listening mode.
7.3.54 C170: LOAD TYPE
C170 LoadType
P
C170 - LoadType
***
R
0 ... 1
D
0
F
This parameter indicates the load type connected to the output terminals.
0:Motor. Output terminals connected to the armature of a DC motor.
1:Inductance. Output terminals connected to an electromagnet.