DCREG2 15P0059B3
DCREG4 USER MANUAL
181/200
7.3.42 C154: ALARM A007 TRIP DISABLING
C154 A007 (Mains)
P
C154 - A007(Mains)
*
R
0 ... 1
D
0
F
It inhibits alarm A007 (Mains Failure).
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
7.3.43 C155: ALARM A008 TRIP MANAGEMENT
C155 A008 (nFdbk)
P
C155 - A008(nFdbk)
***
R
0 ... 2
D
0
F
This parameter manages alarm A008 (Speed Feedback Failure) trip.
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
2:Switch to Varm. The alarm is disabled, but a speed feedback loss will cause
the automatic switching of the speed feedback from TACHO or ENP/NR to
ARMATURE feedback. If this happens, also warning W002 (Speed Fdbk
switched to Varm) will trip. To reset it, disable the ENABLE digital input.
7.3.44 C156: ALARM A010 TRIP DISABLING
C156 A010 (ArmOV)
P
C156 – A010(ArmOV)
***
R
0 ... 1
D
0
F
This parameter inhibits alarm A010 (Armature OverVoltage) trip.
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
7.3.45 C157: ALARM A016/017 TRIP DISABLING
C157 A016/7 ( VAC)
P
C157 - A016/7( VAC)
***
R
0 ... 1
D
0
F
It inhibits both alarm A016 (Mains OverVoltage) and A017 alarm (Mains
UnderVoltage).
0:Included. The two alarms are enabled.
1:Excluded. The two alarms are disabled.
7.3.46 C158: ALARM A027 TRIP DISABLING
C158 A027 (SLink)
P
C158 - A027 (SLink)
***
R
0 ... 1
D
1
F
It inhibits alarm A027 (Serial Link Failure) trip.
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.