II - 22
Design of W-ECO MULTI SYSTEM
2
TD831077
3. Electrical Wiring
(5) Use shielded wires for inter-unit control wiring (c)
and ground the shield on both sides, otherwise
misoperation from noise may occur.
All wiring except inter-unit control wiring (c) has
polarity.
Connect wiring as shown in Section 5-3 “Wiring
System Diagrams”.
Shielded wire
0797_M_I
ground
ground
Loose wiring may cause the
terminal to overheat or result in
unit malfunction. A fire hazard
may also exist. Therefore,
ensure that all wiring is tightly
connected.
When connecting each power wire to the corresponding
terminal, follow the instructions on “How to connect wiring to
the terminal” and fasten the wire securely with the fixing
screw of the terminal plate.
How to connect wiring to the terminal
■ For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm
and tightly twist the wire ends.
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screwdriver.
Stranded wire
Ring
pressure
terminal
Strip 10 mm
1193_M_I
Wire
Special
washer
Screw
Ring pressure
terminal
Terminal plate
Screw and
Special washer
Ring
pressure
terminal
Wire
1107_M_