EasyManuals Logo

Schaltbau CP Series User Manual

Schaltbau CP Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
2021-04-12 / V1.1
Contactors CP Series – Installation and Maintenance Instructions
Installation
8.5 Checks
After the installation, perform the following checks:
X
Check that the contactors are correctly installed
on the mounting plate or mounting frame and
tightly screwed in place.
X
Check that the connecting cables or busbars are
correctly installed and t tightly at the main con-
tacts.
X
Check that the control wires of the coil terminals
are correctly installed and have the correct polar-
ity.
X
Check that the control wires are correctly connect-
ed to the auxiliary switches.
X
Check the correct assignment and function of the
auxiliary switches using a continuity tester.
X
Check that the earthing cable is correctly installed
and ts tightly at the earthing terminal.
X
Ensure that the arc chambers are latched securely
(only for devices with arc chambers).
X
Switch the contactor several times without electric
load in the main circuit.
X
Check the pull-in and drop-o voltage based on
the Schaltbau specications. See catalogue C40.
The catalogue is available under:
https://www.schaltbau.com/en/media-library/
X
Check the routing of the wiring.
- Wires must not be squeezed or bent.
- If applicable bundle and secure wires using ca-
ble ties.
X
After every installation or after maintenance, check
the contactor for correct operation in accordance
with the following standards:
- EN/IEC 60077-2
- EN/IEC 60947-4-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schaltbau CP Series and is the answer not in the manual?

Schaltbau CP Series Specifications

General IconGeneral
BrandSchaltbau
ModelCP Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals