26
Technical Data
Type 024.16.720
7.7. Factory settings of the positioner
Functions can be activated via DIP switches:
Function Parameter Value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Select characteristic FREE
1)
DIR.CMD
Effective direction set-point value rise
Table 4: Factory settings - Functions I
Functions can be activated via communications software:
Function Parameter Value
INPUT
Set-point value input 4 ... 20 mA
DIR.ACTUATOR
Effective direction actual value rise
SPLITRANGE
Function deactivated
Signal split range below
Signal split range above
0 %
100 %
X.LIMIT
Function deactivated
Stroke limit below
Stroke limit above
0 %
100 %
X.TIME
Function deactivated
Actuating time Open
Actuating time Closed
(1 s) values determined by X.TUNE
(1 s) values determined by X.TUNE
After implementation of RESET:
1 s
X.CONTROL
Deadband
Openamplicationfactor
Closeamplicationfactor
1,0 %
(1) values determined by X.TUNE
(1) values determined by X.TUNE
After implementation of RESET: 1
SAFE POSITION
Safety position 0 %
SIGNAL ERROR
Function deactivated
Sensor break detection set-point value OFF
BINARY INPUT
Binary input function
Operating principle of binary input
Safety position
Normally open
OUTPUT
(optional)
Norm signal output: Parameter
Norm signal output: Type
Position
4–20mA
Table 5: Factory settings Functions II
1)
without change to the settings via the communications software a linear characteristic is stored in FREE.