43
Electrical Installation 24 V DC
Type 024.16.720
11.3. Electrical installation with cable gland
DANGER!
Risk of electric shock!
Before reaching into the device or the equipment,• switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety regulations for electrical equipment!•
11.3.1. Designation of the screw-type terminals
1
2*
3*
4
5
6
7
Fig. 27: Connection of screw-type terminals
11.3.2. Connection of the positioner Type 024.16.720
The screw-type terminals can be accessed by unscrewing the body casing (stainless steel).
Push the cables through the cable gland.
Connect the positioner according to the following tables:
Inputsignalsfromthecontrolcentre(e.g.PLC)
Terminal Conguration External circuit
4
5
Set-point value +
Set-point value GND
4
5 GND
+ (0/4 ... 20 mA)
1
Binary input +
1 + 0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
with reference to terminal 7 (GND)
Table 17: Assignment of screw-type terminals - input signals of the control center - cable gland