43
Electrical Installation 24 V DC
Type 024.16.720
11.3. Electrical installation with cable gland
DANGER!
Risk of electric shock!
Before reaching into the device or the equipment,• switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety regulations for electrical equipment!•
11.3.1. Designation of the screw-type terminals
1
2*
3*
4
5
6
7
Fig. 27: Connection of screw-type terminals
11.3.2. Connection of the positioner Type 024.16.720
→ The screw-type terminals can be accessed by unscrewing the body casing (stainless steel).
→ Push the cables through the cable gland.
→ Connect the positioner according to the following tables:
Inputsignalsfromthecontrolcentre(e.g.PLC)
Terminal Conguration External circuit
4
5
Set-point value +
Set-point value GND
4
5 GND
+ (0/4 ... 20 mA)
1
Binary input +
1 + 0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
with reference to terminal 7 (GND)
Table 17: Assignment of screw-type terminals - input signals of the control center - cable gland