6
Electrical installation
Connecting MFE72 fieldbus interface inputs/outputs
Manual – EtherCAT
®
Interfaces, Field Distributors
54
6.6.2 Connection via M12 plug connector
For MFE72 fieldbus interfaces with 4 digital inputs and 2 binary outputs: DIP S1/1 = "OFF"
NOTICE
Loss of the guaranteed degree of protection if the screw plugs in the unused M12
connections are not installed or not installed correctly.
Damage to the fieldbus interface.
Seal all unused M12 connections with screw plugs.
Connect sensors and actuators using either M12 sockets or terminals.
Connect two-channel sensors and actuators to DI0, DI2 and DO0.
DI1, DI3 and DO2 can no longer be used.
L/A
X11 IN
X12 OUT
L/A
DI0
DI2
GND
[1]
GND
DI1
24 V
(VO24)
24 V
(VO24)
24 V
(V2I24)
DI2
1
2
3
5
4
1
2
3
5
4
DI0
X11
EherCAT
p
IN
X12
EherCAT
p
OUT
DI3
DO0
DO1
DI4
DI5
GND2
GND2
DO1
DO1
1
2
3
5
4
1
2
3
5
4
DO0
24 V
(V2I24)
DI1
DI3
18014407325572875
[1] Do not use DI0 in combination with field distributors MFZ26J and MFZ28J.
25809148/EN – 01/2019