14
Service
Bus diagnostics with MOVITOOLS MotionStudio
Manual – EtherCAT
®
Interfaces, Field Distributors
115
"ERR"
LED lights
up green
1x
Prerequisite:
"RUN" LED flashes green (slave is in PRE-OPERATIONAL status).
"RUN" LED lights up green 1× (slave is in SAFE-OPERATIONAL
status).
An unprompted state change has occurred. Repair the configuration
error and start the bus in the master again.
Switch the slave to OPERATIONAL state.
Start the process data communication.
"ERR"
LED
flashes
Prerequisite:
"RUN" LED flashes green (slave is in PRE-OPERATIONAL status).
"RUN" LED lights up green 1x (slave is in SAFE-OPERATIONAL
status).
Invalid configuration. Repair the configuration error and start the bus in
the master again.
Switch the slave to OPERATIONAL state.
Start the process data communication.
14.2 Bus diagnostics with MOVITOOLS
®
MotionStudio
Bus
diagnostics
with
MOVITOOL
S
MotionStud
io
14.2.1 Fieldbus diagnostics with parameter tree
The MF72A fieldbus interface has a diagnostic interface for startup and diagnostics.
This interface allows for bus diagnostics with the parameter tree in the SEW software
MOVITOOLS
®
MotionStudio.
1. Connect the PC/laptop to the MFE fieldbus interface (see chapter "Connecting
PC").
2. Perform an online scan.
25809148/EN – 01/2019