Operating Instructions – MOVITRAC® LT Option Cards
35
9
Operation
Converter card
9.5 Operation
9.5.1 Applications requiring 3 digital inputs and 1 analog input
This is the default setting of the drive. The analog input is connected to terminal 6 of the
converter card and this connects straight to the drive’s analog input and works as
standard.
9.5.2 Applications requiring 4 digital inputs
The drive needs to be set up for 4 digital inputs. Further information on this setup can
be found under the following parameters in the corresponding operating instructions:
•MOVITRAC
®
LTP: Parameter P2-01
•MOVITRAC
®
LTE-B: Parameter P-15
The 4th digital input is activated by one of the following options:
applying 0 10 volts to terminal 6
applying AC 110 V to terminal 13