10 OVERVIEW OF PARAMETERS
Parameter Description
QaPol The analog output signal can be inverted.
Normal = Analog output signal as congured.
Example: QaLow 4 mA/0 V and QAHigh 20 mA/10 V.
Invert = Analog output signal is inverted.
Example: QaLow 20 mA/10 V and QAHigh 4 mA/0 V.
QaHigh Input of the ll level in mm/°C for 20 mA / 10 V signal
(QaHigh > QaLow).
QaLow Input of the ll level in mm (inch)/°C (F) for 4 mA / 0 V
signal.
QaFail Output behavior as per NE43 in the event of a fault (func-
tion only available when current output has been selected
under QaTyp).
3.5 mA = Analog current output is set to 3.5 mA in the
event of a fault.
21.5 mA = Analog current output is set to 21.5 mA in the
event of a fault.
SimQa See “8.5.9 Testing the conguration”.
Disp A/B Display settings.
See: “8.5.2 Setting an alternating display of measurands
(DispA and DispB)”.
UnitLv Level display unit mm/inch.
UnitTm Temperature display unit °C/°F.
SimLvl See “8.5.9 Testing the conguration”.
Setting the level to be simulated.
SimTmp See “8.5.9 Testing the conguration”.
Setting the temperature to be simulated.
Offset See “8.5.11 Setting the offset”.
Lock See “8.5.6 Locking the display with a password”.
AutoCal See “7 Commissioning”.
Filter See “8.5.8 Filtering measured values”.
TrsHld The factor which determines how strong a signal has to be
in order to be recognized by the device. The value range
lies between 20% and 500%.
The default is 100%. Only shown if password entered.
20% = high sensitivity
100% = standard
500% = low sensitivity
Adapt See “8.5.7 Setting the medium adjustment”.
CalEmp Empty calibration.
See “7 Commissioning”.
Reset Resetting the calibration for: empty adjustment, threshold,
and lter settings.
SigQa1 See “8.5.10 Evaluating signal quality”.
SigQa2 See “8.5.10 Evaluating signal quality”.