Wire switching inputs “External input 1 and 2” of the CLV69x in the CDB650-204 connection module
CLV69xCDB650-204
PNP sensor
U
V
GND
3.32K
6.64K
U
e
= max. 32V
18
SGND
8
Shield
11
U
IN
*
X Name
Out
GND
S3
e.g. photoelectric
sensor
CMC600
U
IN
*
a) Sensor supplied via CDB650-204
b) Sensor connected volt-free and supplied externally
d) Switch connected volt-free and supplied externally
Connection of the switch as under b)
Serial Aux
(RS-232)
ON
OFF
S3: SGND-GND
No
YES
S4: CMC
Ue
The output states of the physical inputs
“EXT. IN 1 and 2“ are transmitted by the
CMC600 automatically in a software-
controlled manner via the connecting cable
to the serial Aux interface of the CLV69x.
The CLV69x implements the status on its
logical inputs “External input 1 and 2”.
“External
input 1,
input 2”
SensGND
c) Switch supplied via CDB650-204
CDB650-204
18 SGND
8 Shield
11
U
IN
*
X
Name
GND
S3
U
IN
*
CMC600
ON
OFF
S3: SGND-GND
No
YES
S4: CMC
U
e
SensGND
CDB650-204
PNP sensor
U
V
GND
18
SGND
8
Shield
11 U
IN
*
X
Out
GND
S3
e.g. photoelectric
sensor
U
V ext
Name
CMC600
U
IN
*
No
YES
S4: CMC
ON
OFF
S3: SGND-GND
U
e
SensGND
Switch S3: SGND-GND
ON: GND of the switching inputs connected
with GND of the CDB650-204/CMC600.
OFF: Sensors on switching inputs of the
CDB650-204/CMC600 connected volt-free.
Reference potential valid for all switching inputs
“SENS/IN 1 ... 2” and optionally “EXT. IN1 and 2”
CDB650-204
16
17
Terminal X Name
EXT. IN 1
EXT. IN 2
Specifications of the switching inputs “Ext. input 1 and 2”
Functional allocation for switching inputs
via SOPAS-ET configuration software.
Logic
Properties
Electrical values
Current to input starts the assigned
function, e.g. start read cycle.
(Default CLV69x: logic active high,
debounce 10mm)
– Opto-decoupled, reverse-polarity
protected
– Can be wired with PNP output of a sensor
– SensGND is the shared, insulated
reference potential for all switching inputs
Low: U
e
≤ 2V; I
e
≤ 0.3mA
High: 6V ≤ U
e
≤ 32V;
0.7mA ≤ I
e
≤ 5mA