13 Technical data
13.1 Data sheet
Safety-related parameters
T
able 137: Safety-related characteristic data - safety capable inputs (I)
Safety capable inputs (I)
Single-channel Dual channel
Without test
pulse
s
1)
With test pulses Without test
pulses
2)
With test pulses
Safety integrity
le
vel (IEC 61508)
SIL 2 SIL 3 SIL 3 SIL 3
SIL claim limit
(IEC 62061)
SILCL 2 SILCL 3 SILCL 3 SILCL 3
Cate‐
gory (ISO 13849-
1)
Category 3 Category 4 Category 4 Category 4
Performance
le
vel (ISO
13849-1)
PL d PL e PL e PL e
PFH
D
(h
-1
) 1 × 10
-9
1 × 10
-9
0.5 × 10
-9
0.5 × 10
-9
PFD
a
vg
4 × 10
-5
4 × 10
-5
4 × 10
-5
4 × 10
-5
MTTF
D
IS
O
13849-1
[years]
500 500 500 500
T
M
IS
O 13849-1
[years]
20 20 20 20
1)
If you are using single-channel safety inputs (I) without test pulses for a safety-related application, then
a pr
otected or separate cabling is required for these safety inputs in order to achieve the safety-related
characteristics. Reason: Short-circuits to the supply voltage or cross-circuits are not detected.
2)
If you are using dual-channel safety capable inputs (I) without test pulses, the safety function must be
requested at least once a year.
Table 138: Safety-related characteristic data - CPU logic processing
CPU logic processing
Safety integrity level (IEC 61508) SIL 3
SIL claim limit (IEC 62061) SILCL 3
Category (ISO 13849-1) Category 4
Performance level (ISO 13849-1) PL e
PFH
D
(
h
-1
) 3 × 10
-9
PFD
a
vg
20 × 10
-5
MTTF
D
IS
O 13849-1
[years]
500
T
M
IS
O 13849-1
[years]
20
13 TECHNICAL DATA
126
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact 8024589/2020-11-10 | SICK
Subject to change without notice