EasyManua.ls Logo

Siemens 6MD85 - Page 644

Siemens 6MD85
1256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
_:751:38 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:22 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:751:32 Definite-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:751:39 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:23 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:751:33 Definite-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:751:40 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:751:34 Definite-T 1:Effected by
binary input
•
no
•
yes
no
_:751:41 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:25 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
644 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents