Addr. Parameter C Setting Options Default Setting
General
_:752:1 Definite-T 2:Mode
•
off
•
on
•
test
off
_:752:2 Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:752:26 Definite-T 2:Dynamic
settings
•
no
•
yes
no
_:752:27 Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:752:8 Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:752:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:752:4 Definite-T 2:Dropout
ratio
0.90 to 0.99 0.95
_:752:101 Definite-T 2:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:752:6 Definite-T 2:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:752:28 Definite-T 2:Effect. by AR
off/n.ready
•
no
•
yes
no
_:752:35 Definite-T 2:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:752:29 Definite-T 2:Effected by
AR cycle 1
•
no
•
yes
no
_:752:36 Definite-T 2:Stage
blocked
•
no
•
yes
no
_:752:14 Definite-T 2:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:752:20 Definite-T 2:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:752:30 Definite-T 2:Effected by
AR cycle 2
•
no
•
yes
no
_:752:37 Definite-T 2:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 645