Addr. Parameter C Setting Options Default Setting
_:11104:1 Point 4:Mode
off
on
test
off
_:11104:40 Point 4:Threshold stage 1 -50°C to 250°C 100°C
_:11104:41 Point 4:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11104:42 Point 4:Threshold stage 2 -50°C to 250°C 120°C
_:11104:43 Point 4:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11104:44 Point 4:Sensor Setting options depend on config-
uration
Point 5
_:11105:46 Point 5:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11105:1 Point 5:Mode
off
on
test
off
_:11105:40 Point 5:Threshold stage 1 -50°C to 250°C 100°C
_:11105:41 Point 5:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11105:42 Point 5:Threshold stage 2 -50°C to 250°C 120°C
_:11105:43 Point 5:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11105:44 Point 5:Sensor Setting options depend on config-
uration
Point 6
_:11106:46 Point 6:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11106:1 Point 6:Mode
off
on
test
off
_:11106:40 Point 6:Threshold stage 1 -50°C to 250°C 100°C
_:11106:41 Point 6:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11106:42 Point 6:Threshold stage 2 -50°C to 250°C 120°C
_:11106:43 Point 6:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11106:44 Point 6:Sensor Setting options depend on config-
uration
Point 7
_:11107:46 Point 7:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
Protection and Automation Functions
7.28 Temperature Supervision
906 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017