Addr. Parameter C Setting Options Default Setting
_:11107:1 Point 7:Mode
•
off
•
on
•
test
off
_:11107:40 Point 7:Threshold stage 1 -50°C to 250°C 100°C
_:11107:41 Point 7:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11107:42 Point 7:Threshold stage 2 -50°C to 250°C 120°C
_:11107:43 Point 7:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11107:44 Point 7:Sensor Setting options depend on config-
uration
Point 8
_:11108:46 Point 8:Sensor location
•
Oil
•
Ambient
•
Turn
•
Bearing
•
Other
Other
_:11108:1 Point 8:Mode
•
off
•
on
•
test
off
_:11108:40 Point 8:Threshold stage 1 -50°C to 250°C 100°C
_:11108:41 Point 8:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11108:42 Point 8:Threshold stage 2 -50°C to 250°C 120°C
_:11108:43 Point 8:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11108:44 Point 8:Sensor Setting options depend on config-
uration
Point 9
_:11109:46 Point 9:Sensor location
•
Oil
•
Ambient
•
Turn
•
Bearing
•
Other
Other
_:11109:1 Point 9:Mode
•
off
•
on
•
test
off
_:11109:40 Point 9:Threshold stage 1 -50°C to 250°C 100°C
_:11109:41 Point 9:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11109:42 Point 9:Threshold stage 2 -50°C to 250°C 120°C
_:11109:43 Point 9:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11109:44 Point 9:Sensor Setting options depend on config-
uration
Point 10
_:11110:46 Point 10:Sensor location
•
Oil
•
Ambient
•
Turn
•
Bearing
•
Other
Other
Protection and Automation Functions
7.28 Temperature Supervision
SIPROTEC 5, High-Voltage Bay Controller, Manual 907
C53000-G5040-C015-9, Edition 11.2017