Commissioning overview
11
Building Technologies 008726_e_en_--
Fire Safety 06.2017
3.1.1 Preparations
κ Compact control panel CI1145 –> see document 008727
– Fit and connect the hardware
κ Control panel CC/CI
according to system documentation:
– Fit power supply unit
– Connect mains cable and supply line
– Fit board holder and attach connection cable
– Set I bus address on all plug-in modules / set switches and bridges
– Possibly, insert RAM and EPROMs on central plug-in module, operating ter-
minal and C bus gateway
– Insert all plug-in modules
– Attach I bus flat cable and 5 V/24 V supply cable via all I bus plug-in modules
– Connect fire controls
– Connect batteries
κ Operating terminal CT11
– Remove shielding hood, insert RAM and EPROMs, or possibly load other
Flash program file
– Set bridges
– Slide in designation strip
– Connect C bus and supply line according to system document
– Fit terminal
κ Plain text display terminal and plain text operating terminal
– Set LON bus address / set switch
– Possibly remove resistor
κ Parallel display, 'Extinguishing' operating unit
– Set device address / possibly remove resistor array
Switching on for the first time
– Establish mains voltage, note safety regulations in chapter 2
– For start-up procedure –> see page 39
3.2 Programming the system
For programming the system –> refer to AlgoWorks online help.