Switching on for the first time
39
Building Technologies 008726_e_en_--
Fire Safety 06.2017
17 Switching on for the first time
1. Check whether the batteries are connected.
2. Establish mains voltage. Note 2 'Safety regulations' chapter.
– The 'CC'/'CI'/'CT' stations load basic configuration stored in the EPROM into
the RAM. This start-up procedure is complete after around 2 minutes.
Control panel module E3X10., battery charging plug-in module E3C011
κ Green 'H1-2' LED on CPU part (1) flashing. Irregular flashing: Illuminated phase
considerably shorter than dark phase (period lasts around 1 second).
κ Green 'H501-2' LED (2) 'Mains operation' lights up.
1
H1-2
H501-2
2
E3X10. E3C011
H501-2
2
Operating terminal B3Q... and/or 'CI' control panel
κ LCD contains the following 'NOTE' (information):
κ 'CT' and 'CC/CI' only communicate with one another once the system configura-
tion has been loaded in the stations.
κ Control panel is ready to localize Sinteso
TM
devices, interactive and/or
AnalogPLUS devices or transfer data from the maintenance PC.