LON plug-in module
21
Building Technologies 008726_e_en_--
Fire Safety 06.2017
7 LON plug-in module
7.1 E3I040 I bus/LON plug-in module
Item Component Preparation Default ex factory
1 'S3' programming switch: I bus ad-
dress
Set in accordance with system documentation Address 0
2 'R60' resistor: 'LON bus' terminator
resistor
If the LON bus is wired as free topology, 'R60' must
be changed to 50 ς, see description in document
001260
100 ς
3 'X30' bridge: Ground fault monitoring
'LON bus'
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
Removed (inactive)
X30
3
S3
R60
1
2