Control plug-in modules
22
Building Technologies 008726_e_en_--
Fire Safety 06.2017
8 Control plug-in modules
8.1 E3L020 'I/O' control plug-in module
Item Component Preparation Default ex factory
1 'S3' programming switch: I bus ad-
dress
Set in accordance with system documentation Address 0
2 'S2' service switch: Activate test LEDs
'H1'....'H16'
Set to 'ON' for commissioning To 'OFF'
1
S3
H1
H16
2
S2
8.2 E3L030 'VdS' control plug-in module
Item Component Preparation Default ex factory
1 'S3' programming switch: I bus ad-
dress
Set in accordance with system documentation Address 0
2
0 ς resistor 'X12': Configure LED4
Use if LED4 (reserve/FBF) is to light up in 'degraded
mode operation'
Not used
3 'R191' resistor: For SST Remove (or change), if an external
extinguishing system is connected which
needs a different value.
3K32 used
Bridges X2/16 -> 18
X2/15 -> 17
In accordance with VdS guideline 2540 (Oct 2008),
SST is no longer permitted via E3L030.
2
X12
R191
S3
1
3