CPUs
13
Building Technologies 008726_e_en_--
Fire Safety 06.2017
5 CPUs
5.1 E3X101 control panel module
NOTE
Take measures to protect against overvoltage when inserting RAM and
EPROMs. Press modules all the way into the base.
Item Component Preparation Default ex factory
1 RAM kit (2x 512Kx8 bits) Z3S070 Insert in pos. 'D11' / 'D12' Not used
0 ς resistor to 'X1'
2 Possible RAM extension K3N010
(1MBx8 bits)
Fit bolt and attach board to connector 'ST10' –
3 Select EPROM kit
CCQ00xxx (2x 512Kx8 bits) or
CCW00xxx (2x 512Kx8 bits)
Insert (note positions for 'ODD' and 'EVEN')
Also refer to description in document 001260
EPROM not used
0 ς resistors to 'X2/3/4/Y5'
4 'S2' programming switch: Battery type
selection
Set to battery make used, see description in docu-
ment 001260
'ALARMCOM' (FIAMM) type
5 'S3' programming switch: 'Battery
charging part' I bus address
Set in accordance with system documentation Address 0
6 'S4' switch: Service functions For 'S4-9' commissioning, set to 'ON': –> red test
LEDs ('H2'...'H7') active
All switches to 'OFF'
7
0 ς resistors 'Y8'/'X8': 'Remote alarm'
contact assignment
Resolder if 'Normally closed contact (NC)' is needed To 'Y8' ('Normally open contact
(NO)')
8 'X60' bridge: 'Control panel' ground
fault monitoring
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
Removed (inactive)
9 'X30' bridge: 'C bus potential' Removed (other participants
monitored)
10 'R178/179' 'R196'...'R199' resistors: C
bus impedance
Adjust if necessary
Used for 110 ς impedance
(G51)
X15
X16
X17
D12
RAM
RAM
EPROM
EPROM
EVEN
ST10
ODD
S2
1
3
2
4
5
S3
S4
6
H2...H7
7
X60
8
X30
9
10
R1xx
X3
Y5
X4
X2
X1
D11
Y8