Operation and floor repeater display
27
Building Technologies 008726_e_en_--
Fire Safety 06.2017
11 Operation and floor repeater display
11.1 B3Q... AlgoPilot operating terminal
For operation of AlgoPilot B3Q... . –> see pages 15 –16
11.2 B3Q321 fire brigade operating unit
Item Component Preparation Default ex factory
1 Shielding hood Remove (refit) Fitted
2 'S3' programming switch: I bus ad-
dress
Set in accordance with system documentation Address 0
3 Shield bridge Possibly fit, depending on installation site Included in B3Q321
2
1
S3
2
3
Then connect data bus and supply cable, for installation –> see document 1393.
11.3 B3R051 parallel display
Item Component Preparation Default ex factory
1 'N3' resistor array Remove from all but 1 device, also see description in
document 001260
Equipped
2 'S1' programming switch: Device
address
Set according to system documentation, device ad-
dress is provided by order of wiring
Address 0 (test procedure)
3 Inscription strips Label according to user data and slide in Not labeled
Produce yourself with DOT
Word templates (document
006516)
1
S1
2
N3
1
24
3
Then connect data bus and supply cable, for installation –> see document 1393.