Operation and floor repeater display
29
Building Technologies 008726_e_en_--
Fire Safety 06.2017
11.6 K3I050 LON/mimic display converter
Item Component Preparation Default ex factory
1 Mounting plate Remove, fit according to system documentation, see
also description in document 001260
Fitted
2 'S3' programming switch: LON bus
address
Set in accordance with system documentation Address 0
3 'S4-1' programming switch: Define
LED states of data bus devices
Set to 'ON' if the LEDs of the data bus devices are to
flash (applies to devices with a 5...8 address only)
To 'OFF'
4 'R1' resistor: 'LON bus' terminator
resistor
When using stub line: If K3I050 is not the last device,
remove resistor 'R1', also see description in document
001260
100 ς used
1
S3
2
S4
R1
3
4
Then refit board on mounting plate, connect data bus and LON bus cable, sup-
ply cable as well as peripherals.
11.7 K3I090 PSA interface board
Item Component Preparation Default ex factory
1 'S1' programming switch, 'X16/17'
bridges, 'R70'...'R73' resistors:
Determination of interface
Set, resolder, depending on application, see descrip-
tion in document 1669
'S1' to 'OFF'
'X16/17' 'open'
'R70'.....'R73' used
2 'X9/10' bridges : For mode of oper-
ation
Set, depending on application, see description in
document 1669
'Open'
3 'X/Y11....15' bridges: For
RAM/EPROM equipment
Set, depending on application, see description in
document 1669
Attached 'Y11', 'X12', 'X13', 'X14',
'Y15'
EPROM: 2x512Kx8 bits
RAM: 2x128Kx8 bits
S1
1
2
X9/10
X16/17
R70...R73
X/Y11...15
3