CPUs
14
Building Technologies 008726_e_en_--
Fire Safety 06.2017
5.2 E3X102/103 control panel module
Item Component Preparation Default ex factory
1 SRAM – E3X102 (2x512Kx8 bits)
E3X103 (4x512Kx8 bits)
2 Flash ROM – Program file
E3X102 CCX00xxx
E3X103 CCY00xxx
3 'S2' programming switch: Battery type
selection
Set to battery make used, see description in docu-
ment 001260
'ALARMCOM (FIAMM)' type
4 'S3' programming switch: 'Battery
charging part' I bus address
Set in accordance with system documentation Address 0
5 'S4' switch: Service functions For 'S4-9' commissioning, set to 'ON': –> red test
LEDs ('H2'...'H7') active
All switches to 'OFF'
6 'S5' programming switch: Service and
horn functions
Set according to description in document 001260 All switches to 'OFF'
7 Bridge 'X61': 'Remote alarm' contact
assignment
Resolder if 'Normally closed contact (NC)' is needed To '2-3' ('Normally open contact
(NO)')
8 'X60' bridge: 'Control panel' ground
fault monitoring
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
Removed (inactive)
9 'X30' bridge: Ground fault monitoring
'C bus'
To 'J1' (not monitored)
10 'R178/179' 'R196'...'R199' resistors: C
bus impedance
Adjust if necessary
Used for 110 ς impedance
(G51)
S2
3
S3
1
Flash-ROM
2
4
S4
5
S5
6
7
X61
X60
8
X30
9
10
R1xx
X15
X16
X17
SRAM