Operation and floor repeater display
30
Building Technologies 008726_e_en_--
Fire Safety 06.2017
11.8 K3I110 LON I/O board
Item Component Preparation Default ex factory
1 'S3' programming switch: LON bus
address
Set in accordance with system documentation Address 0
2 'X30' bridge: Ground fault monitoring
'Inputs'
Set according to system documentation, see also
description in document 001260
To 'right' (not monitored)
3 'R1' resistor: 'LON bus' terminator
resistor
When using stub line: If K3I110 is not the last device,
remove resistor 'R1', also see description in document
001260
100 ς used
4 Bridge 'X39': Relay test Set to 'left' for test –> all relays approved, also see
description in document 001260
To 'right' (all relays blocked)
5 'X21' bridge: Activate test LEDs
'H1'....'H16'
Set to 'left' for commissioning, also see description in
document 001260
To 'right' (service LEDs deac-
tivated)
5
X39
4
S3
1
X30
2
R1
3
H1
H16
X21
Then connect data bus and LON bus cable, supply cable as well as peripherals
and fit.
11.9 B3Q580 plain text display terminal
Item Component Preparation Default ex factory
1 'S3' programming switch: LON bus
address
Set in accordance with system documentation Address 0
2 'S4-1' programming switch: Buzzer off For 'S4-1' commissioning, set to 'ON' To 'OFF'
3 'R1' resistor: 'LON bus' terminator
resistor
When using stub line: If B3Q5xx is not the last de-
vice, remove resistor 'R1', also see description in
document 001260
100 ς used
4 Designation strips included in kit
Z5B710...750
Slide in Please order separately, or
produce yourself with DOT
Word templates (document
006516)
2
S3
R1
3
4
S4
1
Then connect LON bus and supply cable, for installation –> see document
001260.