Control plug-in modules
24
Building Technologies 008726_e_en_--
Fire Safety 06.2017
8.5 E3G070 'universal' control plug-in module
Item Component Preparation Default ex factory
1 'S3' programming switch: I bus ad-
dress
Set in accordance with system documentation Address 0
2 'S2' service switch: Activate test LEDs
'H1'....'H11'
Set to 'ON' for commissioning To 'OFF'
3
0 ς resistors 'X12/13', 'Y12/13': Pro-
gram FÜ alarm/fault
Possibly resolder according to system documentation,
see also description in document 001260
To 'Y12' FÜ alarm as normally
open contact (NO) to 'Y13' FÜ
fault as normally closed contact
(NC)
4 'X60' bridge: 'Control panel' ground
fault monitoring
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
Removed (inactive)
4
X60
S3
1
2
3
H1
H11
Y13
Y12
S2