Commissioning
Detailed commissioning steps
10
100 | 118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
10.8.8.2 Switch on zone
1. Select 'Topology' > 'Detection tree' > 'Area' > 'Section' > 'Zone' in the main
menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'On' command.
The yellow 'ISOLATION' LED goes out.
The 'Zone' is switched on.
10.8.9 Restarting the detector line
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
If necessary, block the outputs temporarily [ 101] before switching off the
station or restarting the station/detector line.
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > 'Station' > 'Module' (line
card) > 'Line'.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Restart line' command.
The detector line is restarted. The following messages are displayed:
'Line starting up'
'Device config.runs'
Start line test
Only test the line and line devices once the following messages have disappeared
from the PMI:
- 'Device config.runs'
- 'System startup completed'