Connectivity and communication with 'Station'
Connecting the PC to the station
9
76 | 118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
5. Set the following values:
'Protocol type': 'UDP'
'Local port': 'Specific Ports', and enter the value range '50067-50070' in the
box.
'Remote port': 'All Ports'
6. Confirm with 'OK'.
The new firewall rule is now configured.
NOTICE
Security vulnerability in operating system due
to open ports
Unauthorized access to your PC
Deactivate the firewall rule configured above after the firmware update.
9.2 Connecting the PC to the station
For most commissioning, maintenance and repair work a PC with installed
Cerberus-Engineering-Tool is required. The figure below shows the connection
between the PC and 'Station'.
Figure 30: Rear panel of operating unit and PC
LAN Ethernet connection
1 Cable, type CAT 5 or CAT 7, crossover, max. 100 m
LAN
1
1