Detailed commissioning steps
10
104 | 118
10.8.17 Switching on test mode
1. Select 'Topology' > ↑ 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The yellow 'DETECTOR TEST' LED lights up.
The element is in test mode.
Element Command
Area ● 'Non-MCP zones det.test'
● 'MCP zones det.test'
↑ Section ● 'Non-MCP zones det.test'
● 'MCP zones det.test'
Zone ● 'Detector test'
10.8.18 Switch on normal operation
There is a shortened procedure for switching individual '
operation. The procedure is described in the following section: 'Switching 'Zone' to
normal operation'
Switching 'Area', 'Section' or 'Zone' to ↑ normal operation
1. Select 'Topology' > ↑ 'Detection tree' in the main menu.
2. Select the element you want to switch to normal operation: 'Area', 'Section' or
'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The element is switched to normal operation.
The yellow 'DETECTOR TEST' LED goes out.
Element Command
Area ● 'Non-MCP zones det.test END'
● 'MCP zones det.test END'
↑ Section ● 'Non-MCP zones det.test END'
● 'MCP zones det.test END'
Zone ● 'Detector test END'
Commands under 'Execute commands'
normal operation at superordinate level for
command in question. Test mode can also be exited in the 'Zone', 'Section' or
'Area', for example.