Commissioning
Detailed commissioning steps
10
104 | 118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
10.8.17 Switching on test mode
1. Select 'Topology' > 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The yellow 'DETECTOR TEST' LED lights up.
The element is in test mode.
Element Command
Area 'Non-MCP zones det.test'
'MCP zones det.test'
Section 'Non-MCP zones det.test'
'MCP zones det.test'
Zone 'Detector test'
10.8.18 Switch on normal operation
There is a shortened procedure for switching individual '
Zones
' to
normal
operation. The procedure is described in the following section: 'Switching 'Zone' to
normal operation'
Switching 'Area', 'Section' or 'Zone' to normal operation
1. Select 'Topology' > 'Detection tree' in the main menu.
2. Select the element you want to switch to normal operation: 'Area', 'Section' or
'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The element is switched to normal operation.
The yellow 'DETECTOR TEST' LED goes out.
Element Command
Area 'Non-MCP zones det.test END'
'MCP zones det.test END'
Section 'Non-MCP zones det.test END'
'MCP zones det.test END'
Zone 'Detector test END'
Commands under 'Execute commands'
You can also switch to
normal operation at superordinate level for
the
command in question. Test mode can also be exited in the 'Zone', 'Section' or
'Area', for example.