EasyManua.ls Logo

Siemens Cerberus PRO FC721 - Connectable C-NET Devices; List of Connectable C-NET Devices

Siemens Cerberus PRO FC721
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
C
-
NET detector line
6
58 | 118
Building Technologies
A6V10211100_f_en_
--
F
ire Safety
2015
-
-
15
6.5.1 Connectable C-NET devices
The table below contains a list of all devices which can be connected to the C-NET
detector line. It also highlights which devices feature an alarm indicator (AI) and to
which an external alarm indicator (Ext. AI) or a sounder base (DBS720) can be
connected.
Device type Type Description AI Ext. AI DBS 720
Heat detector HI720
Heat detector for demanding
applications
X X X
HI722 Heat detector for standard applications X X X
Flame detector FDF241-9
Flame detector with three sensors for
demanding applications with many
deceptive phenomena
X X
Smoke detector FDL241-9
Linear smoke detector for demanding
applications with many deceptive
phenomena
X X
OP720
Optical smoke detector for standard
applications with few deceptive
phenomena
X X X
Multi-sensor
detector
OH720 Simple optical-thermal point detector X X X
OOH740
Optical-thermal multi-sensor fire
detector for demanding application
X X X
OOHC740
Optical-thermal multi-sensor fire
detector with CO measurement
X X X
OOH740-A9-Ex
2
Optical-thermal multi-sensor fire
detector with ambient supervision with
collective DualProtocol and FDnet/C-
NET. For areas at risk of explosion
X X X
Aspirating smoke
detector
FDA221
Aspirating smoke detector up to a
monitoring area of 500 m
2
X X X
FDA241
Aspirating smoke detector up to a
monitoring area of 800 m
2
X X X