Remove or replace non
-
stationary C
-
N
ET devices
Replacing non
-
stationary C
-
NET devices of the same type
11
109 |
118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
201
5
-
-
15
11.4 Replacing non-stationary C-NET devices of the
same type
Procedure
Switching on test mode
Replace C-NET device
Switch on normal operation
Connect PC to the 'Station'
Load configuration from the 'Station' to the PC
Disconnect PC from the 'Station'
You will find information about the individual steps in the following chapters and the
chapters to which reference is made below.
11.4.1 Replacing the C-NET device
1. Remove the C-NET device you want to replace from the base.
2. Wait approx. 20 seconds.
3. Insert the new C-NET device of the same type.
The internal alarm indicator flashes for 10 seconds following successful
replacement.
Proceed as follows if the alarm indicator does not flash:
1. Ensure that you wait long enough before inserting.
2. Check whether other C-NET devices are missing on the detector line.
3. Check whether a device that is not of the same type has been inserted. If this is
the case, insert a device of the same type.
4. Restart the C-NET line.