EasyManuals Logo

Siemens FC18 Series User Manual

Siemens FC18 Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Operating Manual of FC18 Controller
Page: 26/70
8. SUPERVISION EVENT HANDLING
Supervision status:
l Supervision indicator turns on
l Supervision events are shown on the LCD as the figure
l Acknowledge/Silence indicator flashing
l Buzzer turns on
How to handle:
1. Press “Acknowledge/Silenceto silence the buzzer:
l Under Level 1 interface, a login interface pops out automatically. Enter
Level 2/3 password and press “OK” to return back to fire alarm window
then press “Acknowledge/Silence”. Now,
Buzzer is mute.
The “Acknowledge/Silence” indicator turns off.
l Under Level 2/3 interface,
Buzzer is mute
The “Acknowledge/Silence” indicator turns off.
2. Find out the supervision location from LCD.
3. Go to the site to handle it if necessary.
4. The supervision event will disappear when supervision signal disappears.
Press “Reset” to turn off the supervision indicator and the controller return to
normal.
Note:
When a supervision event occurs together with another event of higher
priority, supervision event cannot be displayed automatically. Enter the
supervision window manually (see “real-time query” function) to handle it.
Fig.7-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC18 Series and is the answer not in the manual?

Siemens FC18 Series Specifications

General IconGeneral
BrandSiemens
ModelFC18 Series
CategoryController
LanguageEnglish

Related product manuals