8. SUPERVISION EVENT HANDLING
Supervision status:
l Supervision indicator turns on
l Supervision events are shown on the LCD as the figure
l Acknowledge/Silence indicator flashing
l Buzzer turns on
How to handle:
1. Press “Acknowledge/Silenceto silence the buzzer:
l Under Level 1 interface, a login interface pops out automatically. Enter
Level 2/3 password and press “OK” to return back to fire alarm window
then press “Acknowledge/Silence”. Now,
Buzzer is mute.
The “Acknowledge/Silence” indicator turns off.
l Under Level 2/3 interface,
Buzzer is mute
The “Acknowledge/Silence” indicator turns off.
2. Find out the supervision location from LCD.
3. Go to the site to handle it if necessary.
4. The supervision event will disappear when supervision signal disappears.
Press “Reset” to turn off the supervision indicator and the controller return to
normal.
Note:
When a supervision event occurs together with another event of higher
priority, supervision event cannot be displayed automatically. Enter the
supervision window manually (see “real-time query” function) to handle it.
Fig.7-1