EasyManua.ls Logo

Siemens FC18 Series - Technical Data

Siemens FC18 Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating Manual of FC18 Controller
Page: 4/70
2. TECHNICAL DATA
Table 1-1
Item Parameter
Max. No. of line cards 8
Max. No. of devices 2016
LCD screen
320×240 pixelsbacklit
No. of programmable input/output on mainboard 2
No. of NAC (0.5mA @24VDC) 1
Max. history records 10000
Max. distance between controllers within FC18-BUS 1000 m
Max. No. of controllers networked within FC18-BUS 16
Max. distance between a controller and a FRT/Mimic driver within
FR18-BUS
1000 m
Max. No of FRT/Mimic driver connected with a controller 32
Auto-mapping function Available(only for detection line and field device)
Battery (not included) Depends on local regulation
Communication interface Special converter module
Input voltage
220 V@3A, 110 V@6A
220 V/50Hz ,110 V/60Hz
Power supply capacity 10 A@24 VDC
Dimension (In: mm) 1000×600×200
Weight (without battery) 34 Kg
Power fuse 220V:3.0 A , 110V:6.0A
Battery fuse 10.0 A (DC)
Operating temperature
0 +40
Storage temperature
–10 +50
Humidity
95%40±2 ℃)
Environment requirement indoor

Table of Contents