Structure and function
28
Building Technologies
009122_e1_en_--
Fire Safety
2015-10-06
3.4.1 Configuration as a collective detector line (GMT)
3.4.1.1 Detectors which can be connected
Different generations of detector can be connected to the input/output module, e.g.:
Collective detector line configured as Siemens/Cerberus:
MS6; only detectors with LED alarm indicator (not incandescent lamps)
MS7
MS9
SIGMACON (SIGMASYS GMT)
AlgoRex DS110x
Special detectors on the collective detector line, configured as
Siemens/Cerberus:
Flame detector S2406, DF119x, FDF2x19
Linear detector A2400, DLO1191, FDL2x19
Neural fire detector FDOOT2419
Intrinsically safe ex detector DS110x-Ex, DF1101-Ex, F911
Titanus ProSens smoke extraction system (only with new resetting board
type E548/c)
Collective detector line configured as SynoLINE300:
Synova300
Third-party products in accordance with 'Industrial conventional'
(Synova300C)
It is not possible to operate Siemens/Cerberus detectors and SynoLINE300
detectors simultaneously on the same detector line. The compatible detector
types are listed in the 'Collective compatibility' chapter and in the 'List of
compatibility'.
See also
Collective compatibility [ 63]