EasyManua.ls Logo

Siemens FDCIO223

Siemens FDCIO223
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting / Installation
51
Building Technologies
009122_e1_en_--
Fire Safety
2015-10-06
5 Mounting / Installation
The procedure followed during mounting depends on whether the input/output
module FDCIO223 is installed with or without a housing.
WARNING
Electrical voltage on output cables!
Mortal danger due to electric shock!
Ensure that the cables are not supplied with voltage during installation.
NOTICE
High temperatures in the module's environment
Module overheating and damage
A minimum clearance of 1 cm must be observed between two modules or
between the module and any other boundary.
5.1 Installation with housing
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way to ensure the connection
is failure-free for the entire service life of the device.
The module can be installed at any location, along with the separate FDCH221
housing.
When installing the module in the housing FDCH221, proceed as follows:
1. Break out the required cable entries.
2. Install housing on a flat surface.
3. Insert cables. If necessary, fasten the cables using the M20 x 1.5 cable glands
or use a different cable entry.
4. If you are using shielded cable, join the shielding to the DBZ1190-AB
connection terminal. The shielding must not touch any extrinsic earthing
potentials or metal parts in the housing.
5. Install the module in the housing using the fixing screws supplied.
6. Connect cables to corresponding terminals (see connection diagram).
7. Close housing using supplied screws.

Table of Contents

Other manuals for Siemens FDCIO223

Related product manuals